PURPOSE:
To verify that the pressure differentials across the environmentally controlled areas are within recommended specified limits for respective area.
PROCEDURE:- This test should be performed by trained or certified personnel.
- Implementation ISO 14644-3:2005 standards.
- Ensure that the HVAC System has been in operation for a minimum of 8 hours.
- To avoid unexpected changes in pressure and to establish a baseline, all doors in the facility must be closed and no traffic is to be allowed through the facility during the test.
- Using a calibrated magnehelic manometers or calibrated digital manometers, measure the pressure differential between the areas as specified in Table below.
- Record the details of all test data.
ACCEPTANCE CRITERIA:
The differentials pressure in the rooms meet the acceptance criteria.